GRPU is conducting weekly Legionella pneumophila sampling in the drinking water system and/or in community buildings. The objectives of this Legionella monitoring plan are to establish the following:
To gain a better understanding of where the Legionella pneumophila is growing and proliferating, samples are being collected from a variety of locations within the city. Samples are collected at locations representative of the distribution system, as well as from hot and cold water locations within buildings. Approximately 20 samples are being collected each week. Sample locations may vary from week to week and repeat sampling will be conducted when Legionella pneumophila positives are identified.
To request sampling, please fill out the Volunteer Legionella Testing Form online and email it to info@GRPUC.org. For your convenience, printed forms are also available at the GRPU service center.
Results containing the general sample locations and Legionella pneumophila concentrations are shown on the GRPU Monitoring Map. The concern level and corrective actions are shown below so customers are able to have a point of reference of the implications for the data. See Homeowner and Building Manager Tips for steps to help avoid risk of exposure to waterborne germs.
Legionella pneumophila (MPN/100mL) |
Concern level |
Corrective action |
Non-detect (<10) |
Baseline or normal |
Keep maintaining best management practices. |
<100 |
Potential for growth |
Repeat monitoring. Measure and document incoming water quality. |
100 – 1,000 |
Possible growth |
Investigate and mitigate risks of growth, system-wide assessment. |
>1,000 |
Indicates growth |
Investigate, mitigate risks of growth, and enhance control measures. |
1 This table is adapted from AIHA guidelines and Bartrand, T. LeChevallier, M., Clancy, J., and G. Burlingame. (2024) Protocol for responding to the detection of Legionella pneumophila in drinking water distribution systems. AWWA Water Science. 2024;6:e1370.
Apr 24 2024 GRPUC Meeting Update (2-minute mark), ICTV
Mar 26 2024 Legionella Monitoring Technical Memo revised
Mar 1 2024 Legionella and Drinking Water Community Workshop Video, ICTV
Mar 1 2024 Legionella Community Workshop Flyer
Feb 14 2024 GRPU Press Release
Jan 26 2024 Legionella Fact Sheet
Jan 24 2024 40-minute presentation by Steve Mattson, W-WW Manager (Minute mark 21:15 through end of the meeting)
Jan 24 2024 Department Head Presentation on Legionella in Grand Rapids
Jan 24 2024 4-minute recap by Julie Kennedy, General Manager